The three-phase
monitoring relays CM-MPS.x1 monitor the phase parameters phase sequence,
phase failure, over- and undervoltage as well as phase unbalance.
·
Rated control
supply voltage Us = measuring voltage :- 3 x 180-280 V AC
·
Rated control
supply voltage Us tolerance :- -15...+10 %
·
Rated frequency:-
50/60 Hz
·
Frequency range
:- 45-65 Hz
·
power
consumption :- 25 mA / 10 VA (115 V AC)
·
Measuring range
Overvoltage :- 3 x 240-280 V AC
·
Measuring range
Undervoltage:- 3 x 180-220 V AC
·
Tolerance of
the adjusted threshold value:- 6% of
full-scale value
·
Rated
operational voltage Ue :- 250 V
·
Minimum
switching voltage / Minimum switching current :- 24 V / 10 mA
·
Ambient
temperature ranges operation :- -25...+60°C
·
Ambient
temperature ranges storage:- -40...+85
°C
·
Isolation data Rated
insulation input circuit / output circuit:- 600 V
·
voltage Ui output
circuit 1 / output circuit 2:- 300 V
·
Basic
insulation input circuit / output circuit :- 600 V
·
Voltage
Sensing Range :- 180 → 280V ac
·
Voltage
Sensitivity :- Overvoltage, Undervoltage
·
Mounting
Type :- DIN Rail
·
Time
Delay :- 0.1 → 30 s, 0s
·
Frequency
Sensing Range :- 45 → 65Hz
·
Minimum
Voltage Sensed :- 180V ac
·
Operating
Temperature Range :- +60˚C
·
Maximum
Voltage Sensed :- 280V ac
|