Autronica Addressable Input Unit BN-500/N + BNB-300/32 sw: 1.0
Mfr.
Part Number
:- Autronica Addressable Input Unit
BN-500/N + BNB-300/32
Manufacturer
:- Autronica
Description :-
Autronica Addressable Input Unit
BN-500/N + BNB-300/32
Full
Description :- With
one monitored input, for connection of external alarm contacts etc. Approved
for use in hazardous areas, zone 2. With SelfVerify.
BN-500/N is an input unit used to interface different types
of signal devices of ON/OFF type onto the detector loop. The unit is for
use in hazardous area zone 2. It must be connected to a loop driver approved
for zone 2.
Max. capacitance on input :- 30 nF
Voltage :- 10 ‐ 27 VDC
Current consumption, stand by :- 0,3 mA
Environmental requirement :- EN 54‐5/EN 54‐7
Degree of protection Membrane inlets PG‐inlets (PG‐13,5) :- IP54
IP67*
Working temperature :- ‐ 20 ‐ +70 °C
Storage temperature ‐55 ‐ +70˚C
Humidity (non condensing):- Max. 95 % RH
BN-300 input unit is used to interface different
types of signal devices of ON/OFF type onto the detector loop. The unit has
been designed for use with Autronica’s fire detection systems, AutroSafe
(version 4.3.1 or newer) and Autroprime (2.1.3 or newer).
There is also a BN-500/N version for use in
hazardous area zone 2. It must be connected to the BSD-310/N loop driver but
does not require an isolator/barrier unit
Voltage :- 10 - 27 VDC
Max. capacitance on input:- 30 nF
Current consumption stand-by :- 0,3 mA
Environmental requirements:- EN 54-5/EN 54-7
Degree of protection Membrane inlets PG inlets (PG-13,5) :- IP54 ,IP67
Working temperature :- -20 - +70 °C
Humidity (non-condensing):- Max. 95% RH
Condition :- Used / Working
Price :- Sales.plcadvance@gmail.com