Mfr. Part Number: |
ABB CI840A 3BSE041882R1 |
Manufacturer: |
ABB |
Description: |
ABB CI840A 3BSE041882R1 |
Full Description: |
· ABB CI840A 3BSE041882R1:- ·
S800 I/O is a comprehensive,
distributed and modular process I/O system that communicates with parent
controllers and PLCs over industry-standard field buses. ·
The CI840 Fieldbus Communication
Interface (FCI) module is a configurable communication interface that
performs operations such as signal processing, gathering of various
supervision information, OSP handling, Hot Configuration In Run, HART
pass-through and configuration of I/O modules. ·
CI840 is designed for redundant
applications. ·
The FCI connects to the
controller by way of the PROFIBUS-DPV1 fieldbus. ·
Module termination units to
use, TU846 with redundant I/O and TU847 with non-redundant I/O. ·
For redundant communication
interface two CI840A, and one TU847 or one TU846 must be ordered. ·
Product Type:- Communication_Module ·
24 V consumption typ.:- 190
mA ·
Temperature, Operating :- 0
to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C ·
Temperature, Storage :- -40
to +70 °C (-40 to +158 °F) ·
Relative humidity :- 5 to
95 %, non-condensing ·
Max ambient temperature :-
55 °C (131 °F), for vertical mounting 40 °C (104 °F) ·
Protection class :- IP20 · ABB 3BSE022462R1 :- ·
The TU847 is a
module termination unit (MTU) for redundant configuration of the field
communication interface CI840/CI840A. ·
The MTU is a
passive unit having connections for power supply, electrical ModuleBus, two
CI840/CI840A and two rotary switches for station address (0 to 99) settings. ·
A ModuleBus Optical Port TB842 can be
connected to TU847 via TB806. ·
Four mechanical
keys, two for each position, are used to configured the MTU for the right
types of modules. ·
Each key has
six positions, which gives a total number of 36 different configurations. ·
TU846/TU847
needs space to the left in order to be removed. ·
Cannot be
replaced with power applied. TU847 is also available in a G3
compliant version (TU847Z). ·
Type :- Redundant
CI840/CI840A, Single I/O ·
Power input :- 24 V d.c.
(19.2 - 30 V) ·
Mounting :- Vertical or
Horizontal ·
ModuleBus current distribution
:- Maximum 5 V 1.5 A Maximum 24 V 1.5 A ·
Acceptable wire sizes :- 0.25
- 2.5mm², 24 - 14 AWG Recommended
torque: 0.5 - 0.6 Nm Stripping
length: 6-7.5 mm, 0.24-0.30 in ·
Rated insulation voltage
:- 50 V ·
Dialectic test voltage :-
500 V ac ·
Temperature, Operating:- 0
to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C ·
Temperature, Storage:- -40
to +70 °C (-40 to +158° F) ·
Relative humidity :- 5 to
95 %, non-condensing ·
Max ambient temperature :-
55 °C (131 °F), for vertical mounting 40 °C (104 °F) ·
Ingress protection :- IP20 |
Condition: |
Used / Working |
Price: |
Sales.plcadvance@gmail.com |