Mfr. Part Number: |
ABB DI810 16ch 24V Input Module |
Manufacturer: |
ABB |
Description: |
ABB DI810 16ch 24V Input Module |
Full Description: |
· 3BSE008508R1 :- ·
This module has 16 digital
inputs. The input voltage range is 18 to 30 volt d.c. and the input current
is 6 mA at 24 V. ·
The inputs are divided into two
individually isolated groups with eight channels and one voltage supervision
input in each group. ·
Every input channel consists of
current limiting components, EMC protection components, input state
indication LED and optical isolation barrier. ·
The process voltage supervision
input give channel error signals if the voltage disappears. The error signal
can be read via the ModuleBus. ·
16
channels for 24 V d.c. inputs with current sinking ·
Two
isolated groups of 8 with voltage supervision ·
Input
status indicators ·
Signal specification:- 24
V d.c. ·
Number of channels :- 16 ·
Input voltage range, "0"
:- -30..+5 V ·
Input voltage range, "1" :- 15..30 V ·
Input impedance :- 3.5 kΩ ·
Isolation:- Groupwise isolated from ground, 2 groups
with 8 channels ·
Filter times (digital, selectable)
:- 2, 4, 8, 16 ms ·
Current limiting :- Sensor
power can be current limited by the MTU ·
Maximum field cable length
:- 600 meters (656 yards) ·
Rated insulation voltage
:- 50 V ·
Dielectric test voltage :-
500 V a.c. ·
Temperature, Operating :- 0
to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C ·
Temperature, Storage :- -40
to +70 °C (-40 to +158 °F) ·
Relative humidity :- 5 to
95 %, non-condensing ·
Max ambient temperature :-
55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) ·
Protection class :- IP20 · ABB 3BSE013230R1 :- ·
The
TU810/TU810V1 is a 16 channel 50 V compact module termination unit (MTU) for
the S800 I/O. ·
The MTU is a
passive unit used for connection of the field wiring to the I/O modules. ·
It also
contains a part of the ModuleBus. ·
The MTU
distributes the ModuleBus to the I/O module and to the next MTU. ·
It also
generates the correct address to the I/O module by shifting the outgoing
position signals to the next MTU. ·
Two mechanical
keys are used to configure the MTU for different types of I/O modules. ·
This is only a mechanical
configuration and it does not affect the functionality of the MTU or the I/O
module. Each key has six positions, which gives a total number of 36
different configurations. ·
Compact Module Termination Unit
2x8 signal terminals. ·
TU810V1 Compact MTU, 50V ·
Channels :- 16 ·
Voltage :- 50 V ·
Mounting detail :- Horizontal
55 ºC (131 °F) ·
Process connections :- 2 x
2 Process power, 5 x 2 Process power (0 V) ·
Dielectric test voltage :-
500 V ac ·
Acceptable wire sizes :- Solid:
0.2 - 4 mm² Stranded: 0.2 - 2.5 mm², 24 - 12 AWG ·
Temperature, Operating :- 0
to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C ·
Temperature, Storage :- -40
to + 70 °C (-40 to +158 °F) ·
Relative humidity :- 5 to
95 %, non-condensing ·
Max ambient temperature :-
55 °C (131 °F), for vertical mounting 40 °C (104 °F) ·
Protection class :- IP20 |